Fort
Introduction Introduction Back Back Add o favourite Favourite český english
www.fort-plasty.cz
 
 
Fort - airconditioning conduits of plastic
modern technologies | reliability | quality ISO 9001
 
 

FORT - PQ line fans

Documents to download

  • FORT – PQ line fans
 
Temperature resistance:
- for agitated air: -15°C to +60°C
- ambient temperature: +40°C

Intended for atmosphere:
Non-explosive or Explosive (zone 1 and zone 2)

Range of usage:
V = 500 – 12.500 m3 per hour
p = 300 – 3.800 Pa

Housing:
Radial made by rotation moulding. Used material PP, PPs, PE, PE-EL.

Impeller:

Radial with backward curved blades put on the motor shaft directly. Used material PP.

Motor:
Standard single speed three-phased electric motors for 400 V in version B5, protection IP55, insulation class F, in version with 2, 4 or 6poles Ball bearing with grease filling for durability life Single phase for order

Regulation:
Frequency converter (for special order)

Delivery components:
Housing, impeller, motor, epoxy painted motor support

Possible accessories:
- damping connectors
- stainless steel clips
- motor cowling
- exhaust extension with grid
- anti vibrafon kit
- frequency converter
- piping from plastics (PVC, PP, PE + modification)

Notice:
- During installation you must fit a condensate drain adapter or at least drill a hole with a diameter of approx. 5 mm at the lowest point of the fan housing
- A suitable thermal protection has to be included into the electric systém

 

Back back to products
Graphics and applications
DUNA Graphics 2005
FORT - PLASTY s.r.o., Hulínská 2193/2a, 767 01 Kroměříž